Guides/Roofing

Roofing

The roof is the most critical element of a building's weather protection. Learn about roof types, minimum pitch per material, battens, counter battens and underlay — and avoid the most common mistakes.

Calculate roof area →📖 ~8 min read

Common Roof Types

Roof typePitchAdvantagesDisadvantages
Gable / duo-pitch (two slopes)18–45°Classic, good run-off, well-understood constructionCold loft / requires ventilation
Hipped roof (four slopes)18–45°Good wind resistance, small gableMore complex to build
Mono-pitch / lean-to (one slope)5–20°Simple construction, contemporary appearanceGreater demands on underlay and membrane
Flat roof1–5°Maximises usable area, roof terrace possibleDemanding waterproofing, high maintenance
Mansard roof30–70° + 15–30°More habitable space in upper storeyComplex construction
RidgeEavesαRoof pitchBattensUnderlayc/c

Minimum Pitch by Roofing Material

Every roofing material has a minimum pitch. Below this, capillary action, wind pressure and water back-splash can drive water into the construction.

Roofing materialMin. pitchRecommendedNotes
Concrete roof tiles15° (27%)25–45°Some profiles 18°. Below 22° (40%) a type-approved underlay must act as the primary barrier.
Clay / terracotta tiles22° (40%)30–45°18° permitted in low-exposure zones. Heavy (~45 kg/m²).
Corrugated / profiled steel sheets7° (12%)14–25°Some trapezoidal profiles from 5°. Fast to install.
Standing seam (steel / aluminium)3° (5%)5–90°Continuous decking required. Popular on contemporary buildings.
Asphalt shingles14° (25%)19–45°9° possible with double underlay (product-dependent).
Green roof / sedummin. 14–15° (25–27%)19–22°150–300 kg/m². Requires robust rafter structure.
EPDM / PVC / TPO membrane1.4° (1:40)3–5°Flat roofs — internal downpipe drainage required below 2°.
Timber shingles / shakes30° (58%)40–60°Traditional. Birch bark under-layer for historic buildings.
💡
Below the manufacturer's recommended minimum pitch (typically 15–22°), a type-approved breathable underlay is required as the primary waterproof barrier. The tiles then act as secondary weather protection only.

Roof Build-up — Cross Section

Roofing (tiles / sheets / membrane)Battens (ventilation / fixing)Counter battensSarking / underlay (wind-tight)Insulation (between rafters)Vapour control layerInternal lining (plasterboard etc.)

Typical insulated pitched roof

Vapour control layer
Fitted on the warm (interior) side. Sd-value ≥ 5–10 m recommended. All laps and penetrations must be taped airtight.
Insulation
Between rafters (e.g. 200–250 mm mineral wool) plus optional external insulation above the rafters.
Sarking / underlay
Wind-tight and driving-rain resistant membrane. Breathable (Sd < 0.1 m) in a vented roof construction.
Counter battens
Fixed along the rafter line, creating a ventilation gap between the underlay and the horizontal battens.
Battens
Horizontal members to which the roofing is fixed. Centres depend on roofing material and pitch.

Batten Centres and Tile Coverage

MaterialBatten c/cBatten sectionCoverage / lap
Concrete tiles 22–25°340–355 mm36×48 mm9–10 tiles/m²
Concrete tiles 30–35°365–375 mm36×48 mm~8.5–9 tiles/m²
Concrete tiles 40–45°375–385 mm36×48 mm~8–8.5 tiles/m²
Clay tiles 22–25°340–355 mm36×48 mm10–14 tiles/m²
Clay tiles 30–40°370–385 mm36×48 mm~9–11 tiles/m²
Trapezoidal steel sheetRafter / purlin c/c50×150 mm purlinsSide lap: typically 1 corrugation (profile-dependent)
Asphalt shingles19 mm plywood deck7–10 strips/m²

Always check the manufacturer's fixing instructions — centres vary between profiles. The eaves batten is typically raised ~20 mm to give the correct angle to the first tile course.

Counter Batten (Ventilation Gap) Height

Minimum ventilation gap between underlay and battens, by pitch and rafter length:

PitchRafter length ≤ 5 m510 m1015 m
10–15°36 mm48 mm≥ 48 mm
15–25°23 mm30 mm36 mm
25–35°23 mm23 mm30 mm
> 35°23 mm23 mm23 mm

Based on SINTEF Byggforsk 525.102 guidance. Standard counter batten thicknesses: 23, 30, 36 mm.

Building Code — Key Requirements

Snow loadThe roof structure must be designed to carry the characteristic snow load for the location. In lowland areas this is typically 0.6–1.5 kN/m²; in upland and northern regions it can reach 3.0–6.0+ kN/m². Always verify the design snow load for your specific site.
Wind loadRoofing materials and cladding must be fixed to resist wind uplift. Corners and eaves experience higher wind loads — use additional fixings in these zones.
VentilationInsulated pitched roofs must have a continuous ventilation gap between the insulation and the underlay — typically 23 mm with a breathable underlay and 48–50 mm with a non-breathable one (pre-accepted design values). Ventilation openings at eaves and ridge are required.
Vapour controlA vapour control layer must prevent condensation forming within the construction. An Sd-value ≥ 5 m is recommended on the warm side. All penetrations and laps must be sealed airtight.
Weather tightnessThe roofing must provide rain resistance. Below the material's minimum pitch, a type-approved underlay must serve as the primary waterproof barrier.
⚠️
Structural roof members (rafters and purlins) require engineering design. Incorrect sizing can result in collapse under snow load. Consult a structural engineer for new-build or heavily loaded roofs.

Calculating Roof Area

The actual roof area is always larger than the building footprint because of the pitch. The formula is:

Rafter length = Half-span / cos(α)
Roof area = Rafter length × Building length × 2 (gable roof)
Example: 10.00 m long × 8.00 m wide building, 30° pitch
Half-span = 4.00 m
Rafter length = 4.00 / cos(30°) = 4.00 / 0.866 = 4.62 m
Roof area = 4.62 × 10.00 × 2 = 92.4
Pitch (α)Equivalent %cos(α)Area uplift
15°27%0.966+3.5%
22°40%0.927+8%
30°58%0.866+15%
40°84%0.766+31%
45°100%0.707+41%

Step by Step: Laying Roof Tiles

Check that rafters and purlins are straight, dry and free from rot. Verify that any changes to the roof build-up do not significantly alter the snow load.

💡
Maximum rafter deviation: 4 mm over 2 m. Check with a straight-edge and string line.

Start from the eaves. Roll out the underlay membrane horizontally with 100150 mm laps on horizontal joints and 200 mm on vertical joints. Tape all laps with the manufacturer's approved tape.

Counter battens (vertical, along each rafter) are fixed over the underlay — 25×48 mm or 36×48 mm — to secure the membrane and create the ventilation gap.

Calculate the correct centres based on tile type and pitch. Start from the eaves with a tilting fillet (eaves batten raised in thickness to set the correct angle for the first tile course). Use the correct batten section — see the table above.

⚠️
Incorrect batten spacing causes either head-lap problems (too close together) or exposed underlap (too wide apart). Measure carefully and use a gauge rod.

Start from the lower left corner. Keep tiles square to the eaves line. Fix tiles in exposed zones (ridge, eaves and verge) in accordance with the manufacturer's requirements for clips and screws.

Material estimate: Number of tiles = (roof area / area per tile) × 1.10 (10% waste allowance).

Ridge tiles are laid with laps in accordance with the manufacturer's instructions (typically ~50 mm) and fixed with screws. Verge details seal the sides. Gutters are sized to the rainfall intensity — a rough rule of thumb is 1 m of gutter per 25 of roof area (varies considerably with local rainfall intensity and roof geometry).

Gutters and Downpipes

Gutter sizeMax roof areaDownpipe size
100 mm half-round~20 m²Ø 75 mm
125 mm half-round~35 m²Ø 87 mm
150 mm half-round~60 m²Ø 100 mm
150 mm square / box~70 m²76×52 mm

Gutter fall: minimum 1:200 (approx. 5 mm per metre).

Common Mistakes

Ready to calculate your roof?

Use the roof calculator to work out the number of tiles, battens, underlay and total material cost.

Open roof calculator →

Frequently asked questions

What is a "square" in roofing?

A roofing square equals 100 sq ft of roof surface. Most shingle bundles cover 33 sq ft, so you need 3 bundles per square.

What is the minimum roof pitch for asphalt shingles?

Asphalt shingles require a minimum 2:12 pitch with special low-slope installation (double underlayment). Standard installation starts at 4:12. Below 2:12 requires a flat roofing system.

What is roofing underlayment and is it required?

Underlayment (felt paper or synthetic) is installed under shingles as a secondary moisture barrier. It is required by most building codes and provides protection if shingles are damaged.

References

Tile and shingle quantities are indicative. Actual coverage per unit depends on the specific product — always confirm with your supplier. Last reviewed: May 2026